Description
Technical Specification :
- Power : 24V DC
- Current : Monitoring current: ≤ 120μA
Maximum operating current: ≤ 170μA - Indicator : Red
Polling: Flash 6 seconds
Alarm: Remain lit
Fault: Flash 2 seconds - Alarm threshold : A2R (54°C to 62°C)(129°F to 144°F)
- Wiring : Two-wire, polarity-free
- Addressing Method : Electrical encoder
- Address Range : 1–254
- Communication Distance : ≤ 1500 m (4921.26 ft)
- Operating Temperature : –10°C to +50°C (+14°F to +122°F)
- Storage Temperature : –20°C to +65°C (–4°F to +149°F)
- Operating Humidity : ≤ 95% RH (no condensation)
- Color : White
- Dimensions (with base) : Φ 100 mm × 50 mm (Φ 3.00″ × 1.50″)
- Weight (with base) : 81 g (0.18 lb)
- Certifications : GB 4716-2005