21.000 د.ع

Addressable Input/Output Module with Passive Output

DHI-HY-1410E Addressable Input / Output Module is a mated product of the Addressable Fire Alarm Control Panel, regulating the normal operation of external fire protection device. It can realize an output control for fire linkage equipment and receive the feedback signals of the fire linkage equipment to monitor the normal operation of the fire linkage equipment. It can be connected with passivity-based control device such as elevator, fire shutter door.

  • Convenient wiring: two-wire, polarity-free.
  • Reliable communication: built-in microprocessor, stable performance.
  • Ultra-low power consumption: ultra-low monitoring current and alarm current.
  • Simple installation: with a plug-in structure, easy to install and construct.

DataSheet_Addressable I-O Module with Passive Output_DHI-HY-1410

Description

Technical Specification :

Electrical

  • Working Voltage : 24V DC
  • Current : Monitoring current: ≤ 150μA
    Operating current: ≤ 9mA
  • Indicator :  • Input indicator: Red LED flashes once every 6 seconds, and flashes once every 2 seconds when malfunctioned
    • Output indicator: Red LED is constantly off when works normally, and flashes once every 2 seconds when malfunctioned

Communication

  • Wiring : Two-wire, polarity-free
  • Addressing Method : Electrical encoder
  • Address Range : 1–254
  • Communication Distance : ≤ 1500 m

Environment

  • Operating Temperature : –10°C to +55°C (+14°F to +131°F)
  • Storage Temperature : –20°C to +65°C (–4°F to +149°F)
  • Operating Humidity : ≤ 95% RH (no condensation)

Construction

  • Color : White
  • Dimensions (with base) : Φ 90 mm × 90 mm × 37 mm (Φ 3.54″ × 3.54″ × 1.46″)
  • Weight (with base) : 120 g (0.26 lb)
  • Certifications : GB16806-2006

Functions:

  • Input detection
    Monitor status of passive, normally open on-off pieces of equipment, i.e., fire damper, flow indicator, pressure switch, and signal valves.
  • Fast response
    When there is a fire alarm, the signal is sent to the control panel within 1 second.
  • Output control
    Passive output port, DC30V/1A pulse output.
  • Input check mode
    Input check mode is available. Enable Input Check Mode by default.
  • Output check mode
    Output check mode is available. Enable Output Check Mode by default.