Description
Technical Specification :
Electrical
- Working Voltage : DC24V
- Current : Monitoring current: ≤ 2mA
Maximum operating current: ≤ 10mA - Indicator : Working: Green indicator flashes every 6 s during polling, flashes quickly during malfunctioned
Alarm: Red indicator remains lit during alarm
Self-test: Yellow indicator remains lit during self-test Mute: Yellow indicator remains lit when Test/Mute Button is pressed - Display Capacity : 999 pieces of alarm information
- Display : 64×128 LCD screen
Communication
- Wiring : Two-wire, polarity-free
- Addressing Method : Electrical encoder
- Address Range : 1–254
- Communication Distance : 1500 m (4921.26 ft)
- Alarm Sound Pressure : 65dB–115dB (A) @ 1m
Environment
- Operating Temperature : –10°C to +40°C (+14°F to +104°F)
- Storage Temperature : –20°C to +65°C (–4°F to +149°F)
- Operating Humidity : ≤ 95% RH (no condensation)
Construction
- Color : White
- Dimensions (with base) : 180.0 mm × 110.0 mm × 32.0 mm (7.09″ × 4.33″ × 1.26″)
- Weight (with base) : 270 g (0.60 lb)
- Compliance Standard : EN54-2
Functions :
- LCD screen
Display fire locations intuitively. - Flexible setting
Fire alarm area display mode can be flexibly set .